Chiller Tonnage Design Parameters for the Plastics Industry
Following are plastics guidelines used to size a chiller to its specific needs. The tables show the normal process chiller guidelines for chillers and towers used primarily in the plastics industry. Blow molding, injection molding and extrusion are the main plastics uses for needing a chiller system. Also included are basic heat exchanger and mechanical uses guidelines for water chillers. For more chiller information: WWW.chillers.com
| Chillers | Towers |
| * 2.4 to 3.0 GPM/ton @ 10F "delta T" | * 85 F Leaving water temperature |
| * 12,000 BTU / HR / TON | * 95F Entering Water Temperature |
| * 20F - 60F Standard Supply Range | * 78F Wet Bulb |
| * Tonnage rating @ 50F supply temperature | * 3 GPM / Ton |
| * 85F Water cooled condenser (entering) | * 15,000 BTU / HR / Ton |
| * 95F Air cooled condenser (entering) | * Consult Manufacturer for other conditions |
Chiller
Tonnage and Electrical Calculations (Plastics, Printing &
Mechanical uses)![]()
Decrease nominal tonnage by approximately 2% per degree below 50F leaving water temperature.
Increase
nominal tonnage by approximately 2% per degree above
50F leaving water temperature.![]()
Heat Load Sizes
Plastics Industry

| Injection Molding | 30# /HR of H.D. Polyethylene ....=(STANDARD) 1 Ton of cooling |
| 35# /HR of L.D. Polyethylene/ Polypropylene ..= 1 Ton of cooling | |
| 40# /HR of Nylon.............................................. = 1 Ton of cooling | |
| 50# /HR of Polystyrene or ABS....................... .= 1 Ton of cooling | |
| 65# /HR of PVC or Polycarbonate................... = 1 Ton of cooling | |
| 70# /HR of P.E.T............................................... = 1 Ton of cooling | |
| Extrusion | 50# /HR of Polyethylene or Polypropylene...... = 1 Ton of cooling |
| 75# /HR of Polystyrene.................................... = 1 Ton of cooling | |
| 80# /HR of PVC................................................. = 1 ton of cooling | |
| Blow Molding | 40# /HR of Polyolefins ......................................= 1 Ton of cooling |
Mechanical & Extrusion Equipment
| Mechanical | Air compressor (No after cooler) ..............................=.16 Ton of cooling/ Hp |
| Air compressor (With after cooler) ..........................= .20 Ton of cooling/ Hp | |
| Vacuum Pump......................................................... = .10 Ton of cooling/ Hp | |
| Hydraulic Cooling ........ .= .1 Ton /Hp or 1.0 Ton of cooling for every 10 Hp | |
| Hot Runner Mold ............................ = 1.0 Ton of cooling/ 10.5 KW of heat | |
| Water Pump in Circuit........................................ .... = .2 Ton of cooling/ Hp | |
| Feed Throat - 400 Ton up machine.... = 1.0 Ton (.5 Ton if below 400 Ton) | |
| Extrusion | Gear box cooling .............................................= 1.0 Ton of cooling/ 100 Hp |
| Feed Throat 3" Screw or less ... .= 1.0 Ton of cooling (above 3" = 2.0 Tons) | |
| Barrel or Screw Cooling .............= 1 Ton of cooling / inch of screw diameter |
Professional Refrigeration Troubleshooter
|
The first hands on Chiller/HVAC/R troubleshooting handbook is out in publication. This is a must have book for you and your service technicians. It will save you time and money along with passing on the vast knowledge of 60 years experience. |
This page was last updated on July 16, 2008
Click on any of the following hyper linked topics - especially if your browser does not support the java navigation bar above.
Chiller technical support for, plastics chillers, printing chillers, oem chillers, MRI chillers, laser chillers, air dryers,, hvac chillers
Chiller sales for,, chiller rental, used process chillers 2-20 ton, used process chillers 25-80 ton, used chillers 90-350 ton, rental chiller 8-80 ton, rental chiler 100-400 tons
About John C Schaub Inc,, chiller service, rates and hours, geographic chiller service regions, customer references
What is a chiller, chiller refrigeration cycle, chiller tonnage equations, chiller tonnage design parameters, size a chiller, chiller sizing
Chiller antifreeze info,, dowtherm, dowfrost, freezepoint mixture, chiller phone support, chiller water treatment, chiller water flow rates, emergency chiller service
|
This site was created and maintained by Jack Schaub |
| Any inquiries please E-mail the Webmaster: chillerservice@comcast.net |
| John C. Schaub Inc. (On line 11/96) 23 Adams St. Mt. Laurel NJ 08054 phone 856-235-2120 fx 856-235-7033 |
| Copyright 1996-2008 |